Current-loop measurement specifications
The data logger makes current-loop measurements by measuring across a current-sense resistor associated with the RS-485 resistive ground terminal.
Resistance to ground input for non-isolated 0-20 mA and 4-20 mA current loop measurements is available in CR6 data loggers with serial numbers 7502 and greater.
Terminal: RG
Maximum Input Voltage: ±16 V
Resistance to Ground: 101 Ω
Current Measurement Shunt Resistance: 10 Ω
Maximum Current Measurement Range: ±80 mA
Absolute Maximum Current: ±160 mA
Resolution: ≤ 20 nA
Accuracy:
- 0 to 40 °C: ±0.14% of reading
- -40 to 70 °C: ±0.26% of reading
See also Current-loop measurements.