RS-232 default settings
The following are factory-default data strings. RS-232 Default settings provides the RS-232 default settings.
MetSENS200
NODE, DIR, SPEED, CDIR, VOLT, STATUS, CHECK
┐Q,021,000.01,090,+05.1,0000,└ 36
Where,
┐: | STX (Start of String character; ASCII value 2) |
Q: |
Node letter |
021: |
Wind direction |
000.01: | Wind speed |
090 |
Corrected direction |
+05.1 |
Supply voltage |
0000 |
Status |
└ | ETX (End of String character; ASCII value 3) |
36 |
Checksum (2 digit Hex Checksum sum figure calculated from the Exclusive OR of the bytes between, and not including, the STX and ETX characters) |
MetSENS300
NODE, PRESS, RH, TEMP, DEWPOINT, VOLT, STATUS, CHECK
┐Q, 1015.3,041,+022.0,+008.5,+05.1,0000,└ 36
Where,
┐: | STX (Start of String character; ASCII value 2) |
Q: |
Node letter |
1015.3: |
Pressure |
041: | Relative humidity |
+022.0: | Temperature |
+008.5: | Dewpoint |
+05.1 |
Supply voltage |
0000 |
Status |
└ | ETX (End of String character; ASCII value 3) |
36 |
Checksum (2 digit Hex Checksum sum figure calculated from the Exclusive OR of the bytes between, and not including, the STX and ETX characters) |
MetSENS500
NODE, DIR,SPEED, CDIR, PRESS, RH, TEMP, DEWPOINT, VOLT, STATUS, CHECK
┐Q,021,000.01,090,1015.3,041,+022.0,+008.5,+05.1,0004,└ 36
Where,
┐: | STX (Start of String character; ASCII value 2) |
Q: | Node letter |
021: | Wind direction |
000.01: | Wind speed |
090: | Corrected direction |
1015.3: | Pressure |
041: | Relative humidity |
+022.0: | Temperature |
+008.5: | Dewpoint |
+05.1: | Supply voltage |
0004: | Status |
└: | ETX (End of String character; ASCII value 3) |
36: | Checksum (2 digit Hex Checksum sum figure calculated from the Exclusive OR of the bytes between, and not including, the STX and ETX characters) |
MetSENS550/MetSENS600
NODE, DIR, SPEED, CDIR, PRESS, RH, TEMP, DEWPOINT, TOTAL PRECIP, PRECIP INTENSITY,
VOLT, STATUS, CHECK
┐Q,021,000.01,090,1015.3,041,+022.0,+008.5, 00000.200,000.200,+05.1,0004,└ 36
Where,
┐: | STX (Start of String character; ASCII value 2) |
Q: | Node letter |
021: | Wind direction |
000.01: | Wind speed |
090: | Corrected direction |
1015.3: | Pressure |
041: | Relative humidity |
+022.0: | Temperature |
0000.200: | Precipitation total |
000.200: | Precipitation intensity |
+05.1 | Supply voltage |
0004 | Status |
└ | ETX (End of String character; ASCII value 3) |
36 | Checksum (2 digit Hex Checksum sum figure calculated from the Exclusive OR of the bytes between, and not including, the STX and ETX characters) |
Setting |
Setting |
Setting |
---|---|---|
PROTOCOL: GILL | AVGLONG: 101 | SENSOR PRECIP: ON3 |
COMMS: RS232 | SENSOR COMPASS: ON1 | UNITS PRECIP: MM3 |
BAUD: 9600 | COMPASSDECL: +000.01 | POWER: 0 |
NODE: Q | SENSOR TEMP: ON2 | PUPMSG STATUS: ON |
OUTFREQ: 1Hz | UNITS TEMP: C2 | PUPMSG REPORT: ON |
MSGMODE: CONT | SENSOR DEWPOINT: ON2 | PUPMSG UNITS: ON |
ASCTERM: CRLF | UNITS DEWPOINT: C2 | MODBUS: RTU |
ECHO : ON | SENSOR PRESS: ON2 | MODADDR: 1 |
ALIGN: 01 | UNITS PRESS: HPA2 | DATABITS: 8 |
SENSOR WIND: ON1 | HASL: +00000.002 | STOPBITS: 1 |
UNITS WIND: MS1 | HASTN: +00000.002 | PARITY: NONE |
NODIR: 0.001 | SENSOR RH: ON2 | MODTERM: 10 |
AVGSHORT: 601 | UNITS RH: %2 | MODICT: 1000 |