ModbusOption (Modbus Option)
An optional parameter that is used to specify the data type of the Modbus variables.
| Code | Description |
|---|---|
| 0 or absent | Default; 32-bit float or Long, the standard ordering of the 2 byte registers are reversed (CDAB). |
| 1 | If the Modbus variable array is defined as a Long, variables are treated as 16-bit signed integers. |
| 2 | If the Modbus variable array is defined as a 32-bit float or a Long, with no reversal of the byte order (ABCD). |
| 3 | If the Modbus variable array is defined as a Long, variables are treated as 16-bit unsigned integers. |
| 10 | Modbus ASCII, 4 bytes, CDAB. |
| 11 | Modbus ASCII, 2 bytes, signed. |
| 12 | Modbus ASCII, 4 bytes, ABCD. |
| 13 | Modbus ASCII, 2 bytes, unsigned. |
Type: Variable