DNPVariation (DNP Variation)

Assigns the Source parameter to a specific variation, which describes the data format within its Object group. Datalogger supported DNP objects and variations:

NOTE: Object 0 device attribute variations are read only and cannot be specified in the DNPVariable instruction. Rather, they are sent only when requested by a master device.

Object Variation Description
0 240 Device attribute, maximum transmit fragment size
0 241 Device attribute, maximum receive fragment size
0 242 Device attribute, OS version
0 243 Device attribute, rev board, TI chip
0 247 Device attribute, station name
0 248 Device attribute, serial number
0 250 Device attribute, product name and model
0 252 Device attribute, name of device manufacturer
0 254 Device attribute, return all devices attributes in single response
0 255 Device attribute, retrieve all of the supported device attribute variation numbers
1 1 Static, Binary Input
1 2 Static, Binary Input with Status
2 1 Event, Binary Input Change without Time
2 2 Event, Binary Input Change with Time
2 3 Event, Binary Input Change with Relative Time
10 1 Static, Binary Output, Packed Format
10 2 Static, Binary Output Status, with Flags
12 1 Binary command, control relay output block (CROB)
20 1 Counter, 32-bit with flag
20 2 Counter, 16-bit with flag
20 3 Counter, 32-bit with flag, delta
20 4 Counter, 16-bit with flag, delta
20 5 Counter, 32-bit without flag
20 6 Counter, 16-bit without flag
20 7 Counter, 32-bit without flag, delta
20 8 Counter, 16-bit without flag, delta
21 1 Frozen counter, 32-bit with flag
21 2 Frozen counter, 16-bit with flag
21 5 Frozen counter, 32-bit with flag and time
21 6 Frozen counter, 16-bit with flag and time
21 9 Frozen counter, 32-bit without flag
21 10 Frozen counter, 16-bit without flag
22 1 Counter event, 32-bit with flag
22 2 Counter event, 16-bit with flag
22 5 Counter event, 32-bit with flag and time
22 6 Counter event, 16-bit with flag and time
30 1 Static, 32-Bit Analog Input
30 2 Static,16-Bit Analog Input
30 3 Static, 32-Bit Analog Input without Flag
30 4 Static, 16-Bit Analog Input without Flag
30 5 Analog input, single precision floating point with flag
32 1 Event, 32-Bit Analog Change Event without Time
32 2 Event, 16-Bit Analog Change Event without Time
32 3 Event, 32-Bit Analog Change Event with Time
32 4 Event, 16-Bit Analog Change Event with Time
32 5 Analog input event, single precision floating point without time
32 7 Analog input event, single precision floating point with time
40 1 Analog output status, 32-bit with flag
40 2 Analog output status, 16-bit with flag
40 3 Analog output status, single precision floating point with flag
41 1 Analog output, 32-bit
41 2 Analog output, 16-bit
41 3 Analog output, single precision floating point
50 1 Read, Time and Date
60 2 Class 1 Data
60 3 Class 2 Data
60 4 Class 3 Data
110 X Octet string; variation parameter is used to declare maximum length of string

Type: Constant