Multiplexers controlled by data logger
For this configuration, SDI-12 is used to measure the vibrating-wire sensors. The vibrating-wire sensors are attached to multiplexers, which are controlled by the data logger.
SDI-12 communications
-
When using SDI-12, multiplexers must be controlled by the data logger.
-
SDI-12 is the only option available for non-Campbell Scientific data loggers.
If using SDI-12 communications, do the following:
-
Access Device Configuration Utility to configure the for SDI-12 communications. Go to the Deployment/Measurement tab in Device Configuration Utility and enter the SDI-12 address, multiplexer type, begin frequency, end frequency, and excitation (see Connecting to Device Configuration Utility and Measurement).
-
Use a CABLE4CBL-L cable to connect the to the multiplexers (see ).
NOTE:SDI-12 uses CLK and RESET on the multiplexer instead of the CLK and RESET address on the .
-
Connect the sensors to the multiplexers. Refer to the spread spectrum data radio/modem manual for more information: https://s.campbellsci.com/documents/us/manuals/rf401a-series.pdf
. -
Use a CABLE4CBL-L cable to connect the multiplexers to the data logger (see Multiplexer to data logger power/control hookup (multiplexer controlled by data logger)).
-
Use a CABLE3CBL-L cable to connect the C1 terminal on the to a control port and ground on the data logger.
-
Connect one end of the power cable to the 12V and G terminals on the and the other end to the 12V and G terminals on the data logger or external power supply. Refer to Power and ground and Data logger wiring for a direct connection for more information.
-
Program the data logger. Campbell Scientific CRBasic data loggers use the
SDI12Recorder()instruction. TheSDI12Recorder()instruction should only be run in the sequential mode for this configuration. See Programming for SDI-12 measurements, SDI-12 example.