AVW200 control of the multiplexer

For most applications, having the AVW200 control the multiplexer is preferable. A CABLE4CBL or MUXSIGNAL cable connects to the multiplexer COM terminals, and another CABLE4CBL cable or the MUXPOWER cable connects to the multiplexer CLK and RESET terminals (see Example AM16/32-series to AVW200 hookup (multiplexers controlled by AVW200)).

NOTE:

When two multiplexers are connected to the AVW200, they share the CLK and RESET lines. Because of this, while one multiplexer is making measurements, the other multiplexer will advance its channels but without making any measurements.