Pulse measurement specifications
Conflicts can occur when a control port pair is used for different instructions (TimerInput()
, PulseCount()
, SDI12Recorder()
, WaitDigTrig()
). For example, if C1 is used for SDI12Recorder()
, C2 cannot be used for TimerInput()
, PulseCount()
, or WaitDigTrig()
.
Sustained Input Voltage without Damage: ±20 VDC
Maximum Counts Per Scan: 232
Input Resistance: 5 kΩ
Accuracy: ±(6 ppm of reading + 0.00001)
Switch closure input
Terminals: C1-C8
Pull-Down Resistance: Configurable in terminal pairs with 100 kΩ
Pull-Up Resistance: Configurable in terminal pairs with 100 kΩ (weak) or 2.2 kΩ (strong)
Maximum Input Frequency: 250 Hz
Minimum Switch Closed Time: 1 ms
Minimum Switch Open Time: 1 ms
Maximum Bounce Time: 1 ms open without being counted
Software Debounce Time: 1 ms
High-frequency input
Terminals: C1-C8
Pull-Down Resistance: Configurable in terminal pairs with 100 kΩ
Pull-Up Resistance: Configurable in terminal pairs with 100 kΩ (weak) or 2.2 kΩ (strong)
Maximum Input Frequency: