Power requirements
Protection: Power inputs are protected against surge, over-voltage, over-current, and reverse power. IEC 61000-4 Class 4 level.
-
Input from Power converter or solar panel
-
*ES1 PS2 energy sources only
-
16 to 32 VDC
-
Input current limit @ 12 VDC:
-
Hold limit 1.2 A @ 20 °C
-
Input voltage must be at least 0.3 V higher than the voltage required to charge the battery; 40 VDC sustained voltage limit without damage. Transient voltage suppressor (TVS) diodes at the BAT and CHG terminals clamp transients to 19 to 21 V and 19 to 40 V respectively. Sustained input voltages in excess of 19 V or 40 V respectively can damage the TVS diodes.
Battery Terminal Characteristics (BAT+ and BAT-):
- Voltage input 12 VDC only
- Hold Current limit 2.5 A @ 20 °C
*Energy Source Class 1 (ES1) and Power Source Class 2 (PS2), as defined in Clauses 5 and 7 of IEC/AS/NZS 62368-1:2022.
External Batteries:
- Float charge on BAT terminal
- 12 VDC
- Valve-regulated, lead-acid (VRLA)
- 2 to 24 Ah battery typical
Vehicle Power Connection: When primary power is pulled from the vehicle power system, a second power supply OR charge regulator may be required to overcome the voltage drop at vehicle start-up.
USB Device Power: Functions that will be active with USB Device 5 VDC include sending programs, adjusting data logger settings, and making some measurements. If USB Device is the only power source, then the CS I/O port and the 12V and SW12 terminals will not be operational.
Internal Lithium Battery: 1/2AA, 1.2 Ah, 3.6 VDC (Tadiran L5902S) for battery-backed memory and clock. 1.5-year life with no external power source.
Average Current Drain:
Assumes 12 VDC on BAT terminals — add 2 mA if using CHG terminals.
- Idle: <1 mA
- Active 1 Hz Scan: 3 mA
- Active 20 Hz Scan: 67 mA
- Serial (RS-232/RS-485): Active + 25 mA
- Ethernet Power Requirements:
- Ethernet 1 Minute: Active + 1 mA
- Ethernet Idle: Active + 4 mA
- Ethernet Link: Active + 47 mA
Wi-Fi Additional Current Contribution at 12 VDC:
Mode |
Wi-Fi Option |
---|---|
Client Mode | 7 mA idle, 70 mA communicating |
Access Point Mode | 62 mA idle, 70 mA communicating |
Sleep IPNetPower() or DevConfig setting to disable) |
<1 mA |