Power output

The data logger can be used as a power source for communications devices, sensors and peripherals. Take precautions to prevent damage to these external devices due to over- or under-voltage conditions, and to minimize errors. Additionally, exceeding current limits causes voltage output to become unstable. Voltage should stabilize once current is again reduced to within stated limits. The following are available:

CAUTION:

The voltage levels at the 12V and switched SW12 terminals, as well as pin 8 on the CS I/O port, are tied closely to the voltage levels of the main power supply. Therefore, if 16 VDC is supplied to the POWER IN 12V and G terminals, the 12V, SW12 terminals, and pin 8 on the CS I/O port will also supply 16 VDC to connected peripherals. This could damage any connected peripheral or sensor not designed to handle that voltage.

  • C or U terminals: can be set low or high as output terminals . With limited drive capacity, digital output terminals are normally used to operate external relay-driver circuits. Drive current varies between terminals. See also Digital input/output specifications.

  • U terminals: can be configured to provide regulated ±2500 mV dc excitation.

See also Power output specifications .