Pulse measurement specifications
Terminals individually configurable for switch closure, high-frequency pulse, or low-level AC measurements.
Conflicts can occur when a control port pair is used for different instructions (TimerInput(), PulseCount(), SDI12Recorder(), WaitDigTrig()). For example, if C1 is used for SDI12Recorder(), C2 cannot be used for TimerInput(), PulseCount(), or WaitDigTrig().
Sustained Input Voltage without Damage: ±20 VDC
Maximum Counts Per Scan: 224
Input Resistance: 5 kΩ
Accuracy: ±(0.02% of reading + 1/scan)
Low-level AC input
Terminals: P1-P2
Minimum Pull-Down Resistance: 10 kΩ to ground
DC-offset rejection: Internal AC coupling eliminates DC-offset voltages up to ±0.05 VDC
Input Hysteresis: 12 mV at 1 Hz
Low-Level AC Pulse Input Ranges:
| Sine wave (mV RMS) | Range (Hz) |
|---|---|
| 20 | 1.0 to 20 |
| 200 | 0.5 to 200 |
| 2000 | 0.3 to 10,000 |
| 5000 | 0.3 to 20,000 |
Switch closure input
Terminals: C1-C8, P1-P2
Pull-Up Resistance: 100 kΩ to 5 V
Event: Low (<0.8 V) to High (>2.5 V)
Maximum Input Frequency: 150 Hz
Minimum Switch Closed Time: 5 ms
Minimum Switch Open Time: 6 ms
Maximum Bounce Time: 1 ms open without being counted
High-frequency input
Terminals: C1-C8, P1-P2
Pull-Up Resistance: 100 kΩ to 5 V
Event: Low (<0.8 V) to High (>2.5 V)
Maximum Input Frequency: