Pulse measurement specifications
Terminals individually configurable for switch closure, high-frequency pulse, or low-level AC measurements.
Conflicts can occur when a control port pair is used for different instructions (TimerInput()
, PulseCount()
, SDI12Recorder()
, WaitDigTrig()
). For example, if C1 is used for SDI12Recorder()
, C2 cannot be used for TimerInput()
, PulseCount()
, or WaitDigTrig()
.
Sustained Input Voltage without Damage: ±20 VDC
Maximum Counts Per Scan: 224
Input Resistance: 5 kΩ
Accuracy: ±(0.02% of reading + 1/scan)
Low-level AC input
Terminals: P1-P2
Minimum Pull-Down Resistance: 10 kΩ to ground
DC-offset rejection: Internal AC coupling eliminates DC-offset voltages up to ±0.05 VDC
Input Hysteresis: 12 mV at 1 Hz
Low-Level AC Pulse Input Ranges:
Sine wave (mV RMS) | Range (Hz) |
---|---|
20 | 1.0 to 20 |
200 | 0.5 to 200 |
2000 | 0.3 to 10,000 |
5000 | 0.3 to 20,000 |
Switch closure input
Terminals: C1-C8, P1-P2
Pull-Up Resistance: 100 kΩ to 5 V
Event: Low (<0.8 V) to High (>2.5 V)
Maximum Input Frequency: 150 Hz
Minimum Switch Closed Time: 5 ms
Minimum Switch Open Time: 6 ms
Maximum Bounce Time: 1 ms open without being counted
High-frequency input
Terminals: C1-C8, P1-P2
Pull-Up Resistance: 100 kΩ to 5 V
Event: Low (<0.8 V) to High (>2.5 V)
Maximum Input Frequency: