Pulse measurement specifications

Terminals individually configurable for switch closure, high-frequency pulse, or low-level AC measurements. See also Digital input/output specifications. Each terminal has its own independent 24-bit counter.

NOTE:

Conflicts can occur when a control port pair is used for different instructions (TimerInput(), PulseCount(), SDI12Recorder(), WaitDigTrig()). For example, if C1 is used for SDI12Recorder(), C2 cannot be used for TimerInput(), PulseCount(), or WaitDigTrig().

Sustained Input Voltage without Damage: ±20 VDC

Maximum Counts Per Scan: 224

Input Resistance: 5 kΩ

Accuracy: ±(0.02% of reading + 1/scan)

Low-level AC input

Terminals: P1-P2

Minimum Pull-Down Resistance: 10 kΩ to ground

DC-offset rejection: Internal AC coupling eliminates DC-offset voltages up to ±0.05 VDC

Input Hysteresis: 12 mV at 1 Hz

Low-Level AC Pulse Input Ranges:

Sine wave (mV RMS) Range (Hz)
20 1.0 to 20
200 0.5 to 200
2000 0.3 to 10,000
5000 0.3 to 20,000

Switch closure input

Terminals: C1-C8, P1-P2

Pull-Up Resistance: 100 kΩ to 5 V

Event: Low (<0.8 V) to High (>2.5 V)

Maximum Input Frequency: 150 Hz

Minimum Switch Closed Time: 5 ms

Minimum Switch Open Time: 6 ms

Maximum Bounce Time: 1 ms open without being counted

High-frequency input

Terminals: C1-C8, P1-P2

Pull-Up Resistance: 100 kΩ to 5 V

Event: Low (<0.8 V) to High (>2.5 V)

Maximum Input Frequency: 250 kHz